摘要
With the influence of the fault current, the current transformers (TAs) on both sides of the transformer differential protection are prone to saturation, which would distort the current waveforms of the transformer and seriously affect the correct operation of the transformer differential protection. To solve the problem of misoperation or operation failure of transformer differential protection caused by TA saturation, the phase relationship characteristics between the currents on both sides of the transformer with different fault types are comparatively analyzed. A novel criterion for transformer differential protection is proposed to identify various faults accompanied by the TA saturation, which is based on the two-dimensional reconstruction of currents on both sides and the reconstructed characteristic trajectories. The results of simulation and experimental tests indicate that the proposed criterion has high reliability and sensitivity, as well as the high anti-saturation ability of TA.
- 单位